Surge Protection Device, 3 Phase, 277/480V AC, 3 Poles, 4 Wires, 120kA - HL4IMA12C

Square D
SKU:
HL4IMA12C
|
UPC:
785901691211
Availability:
In Stock

Log in for pricing

(No reviews yet)
Current Stock:
Surge Protection Device, Metallic, Gray, Amps 60 A, Depth 5.59 in, Enclosure NEMA Rating 2
Country of Origin:
Mexico
Item:
Surge Protection Device
Mounting Style:
For I-Line Panelboards
Phase:
3
Voltage:
277/480V AC
Number of Poles:
3
Voltage Protection Rating:
1200V (L-G,N-G), 1500V (L-N), 2000V (L-L)
Filtering / Nonfiltering:
Filtering
Number of Wires:
4 Wires
Modes of Protection:
L-G, L-L, L-N, N-G
Max. Surge Current per Mode:
120 kA
Max. Surge Current Per Phase:
120kA
Max. Surge Current per Phase:
120 kA
Nominal Discharge Current:
20 kA
Short Circuit Current Rating:
200kA
Modular:
Yes
Filtering:
Yes
Max. Continuing Operating Voltage:
320V AC
Enclosure NEMA Rating:
NEMA 2
Enclosure Material:
Metal
Length:
12.16 in
Depth:
5.59 in
Width:
13.46 in
Wire Gauge:
6 AWG
Includes:
Dry Contacts
Modular / Nonmodular:
Modular
Standards:
CSA C22.2 No 5-09, CSA C22.2 No 8
Color:
Gray
UL SPD Type:
Type 2
Amps:
60 A
System Connection:
Parallel
Basic Material:
Metallic
Length (Straight Wireway):
12.16 in
Status Indicator:
Audible Alarm, LED Light
Includes Surge Counter:
Yes
Breaking Capacity Code:
HL
Mounting Support:
panel mounting
Surge Current:
120 kA
Device Short Name:
IMA
Line Rated Current:
60 A
Connections - Terminals:
I-Line line || lugs ground AWG 6 copper 4 N.m || lugs neutral AWG 6 copper 4 N.m
[Uc] Maximum Continuous Operating Voltage:
150 V
Cable Length:
483 mm
Provided Equipment:
alarm enable/disable switch || surge counter || circuit-breaker
Local Signalling:
status LED green per phase normal operation || status LED red per phase fault
Breaking Capacity:
50 kA
Trip Unit Technology:
thermal-magnetic
Package Quantity:
1