- Country of Origin:
- France
- Item - Relay:
- IEC Style Overload Relay
- Item:
- Overload Relay
- Use With - Contactors and Starters:
- Mfr. Series LC1D40A to LC1D65A Contactors
- Current Range:
- 48.0 to 65.0A
- Overload Relay Current Range:
- 48 to 65A
- NEMA Size:
- Not Applicable
- Trip Class - Overload:
- 20
- Width:
- 2.17";Number of Poles=3"
- Height:
- 2.76";Sensing Method=Bimetallic"
- Reset Type - Relay:
- Manual
- Depth:
- 4.84";Kit Required for Retrofit Mtg.=No"
- Features:
- Single Phase Sensitivity; Differential
- Standards:
- CSA C22.2 No 60947-4-1, CSA C22.2 No 60947-5-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, REACH, RoHS, UL 60947-4-1, UL 60947-5-1
- Body Height - Relay:
- 2.76 in
- Trip Class:
- 20
- Body Width - Relay:
- 2.17 in
- Overall Height - Relay:
- 2.76 in
- Separate Mounting:
- Yes
- Body Depth - Relay:
- 4.84 in
- For Use With:
- TeSys D LC1D40A thru LC1D65A Contactors, Direct Mounting to LC1 with Ever Link Terminations D40A-D65A
- Starter Type:
- IEC
- Flame Retardance:
- V1 conforming to UL 94
- Permissible Current:
- 3 A 120 V AC-15 signalling circuit || 0.22 A 125 V DC-13 signalling circuit
- Network Frequency:
- 0 to 400 Hz
- Mounting Support:
- plate, with specific accessories || rail, with specific accessories || under contactor
- Device Short Name:
- LRD
- Control Type:
- Red push-button stop || Blue push-button reset
- Tightening Torque:
- control circuit 1.7 N.m screw clamp terminals || power circuit 5 N.m EverLink BTR screw connectors
- Ip Degree Of Protection:
- IP20 conforming to IEC 60529
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV
- Connections - Terminals:
- control circuit screw clamp terminals 2 1-2.5 mm² flexible without cable end || control circuit screw clamp terminals 2 1-2.5 mm² flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm² solid without cable end || power circuit
- Product Certifications:
- IEC || UL || CSA || CCC || EAC || DNV-GL || RMRS || EU-RO MR || LROS (Lloyds register of shipping) || UKCA
- Product Or Component Type:
- differential thermal overload relay
- Product Compatibility:
- LC1D50A || LC1D65A
- Tripping Threshold:
- 1.14 +/- 0.06 Ir IEC 60947-4-1
- Ambient Air Temperature For Storage:
- -60-70°C
- Phase Failure Sensitivity:
- tripping current 130 % of Ir on two phase, the last one at 0
- Mechanical Robustness:
- shocks15 Gn for 11 ms IEC 60068-2-7 || vibrations4 gn IEC 60068-2-6
- Relay Application:
- motor protection
- [Ue] Rated Operational Voltage:
- 690 V AC 0 to 400 Hz power circuit IEC 60947-4-1
- Associated Fuse Rating:
- 4 A gG signalling circuit || 4 A BS signalling circuit
- Temperature Compensation:
- -20-60°C
- Thermal Protection Adjustment Range:
- 48-65 A
- Product Name:
- TeSys LRD || TeSys Deca
- Dielectric Strength:
- 1.89 kV 50 Hz IEC 60947-1
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Ambient Air Temperature For Operation:
- -20-60°C without derating IEC 60947-4-1
- Range:
- TeSys || TeSys Deca
- Thermal Overload Class:
- class 20 IEC 60947-4-1
- Climatic Withstand:
- IACS E10
- Network Type:
- DC || AC
- [Ui] Rated Insulation Voltage:
- power circuit 600 V CSA || power circuit 600 V UL || power circuit 690 V IEC 60947-4-1
- [Ith] Conventional Free Air Thermal Current:
- 5 A signalling circuit
- Maximum Voltage Rating:
- 690V AC
- Minimum Overload Relay Current Setting:
- 48 A
- Relay Style:
- IEC
- Maximum Operating Temperature:
- 140 Degrees F
- Compatible with Series:
- TeSys Deca
- Body Depth:
- 4.84 in
- Includes Mounting Hardware:
- Not Applicable
- Auxiliary Contact Form:
- 1NO/1NC
- IP Rating:
- IP20
- Terminal Connection Type:
- Screw Clamp Terminals
- Maximum Overload Relay Current Setting:
- 65 A
- Overload Protection Type:
- Thermal
- Mounting Style:
- Direct To Contactor
- Minimum Operating Temperature:
- -4 Degrees F
- Body Height:
- 2.76 in
- Body Width:
- 2.17 in
- Reset Type:
- Auto, Manual
- Overall Height:
- 2.76 in
- Package Quantity:
- 1