Overload Relay, 1.80 to 2.60A, Class 10, 3P - LR2K0308

Schneider Electric
SKU:
LR2K0308
|
UPC:
785901883067
Availability:
In Stock

Log in for pricing

(No reviews yet)
Current Stock:
Overload Relay, Auxiliary Contact Form 1NO/1NC, Maximum Overload Relay Current Setting 2.6 A, Minimum Overload Relay Current Setting 1.8 A, Trip Class 10A, Maximum Voltage Rating 250V DC (Signaling Circuit), 690V AC (Signaling Circuit), NEMA Size Not Applicable, Number of Poles 3, Reset Type Auto, Manual, Mounting Style Direct To Contactor, Terminal Connection Type Screw Clamp Terminals, Compatible with Series TeSys Deca, TeSys K, Relay Style IEC, Overload Protection Type Thermal
Country of Origin:
Czechia
Item - Relay:
IEC Style Overload Relay
Item:
Overload Relay
Current Range:
1.80 to 2.60A
Use With - Contactors and Starters:
LC7K, LP1K, LP4K Contactors, Mfr. Series LC1K
Overload Relay Current Range:
1.80 to 2.60A
NEMA Size:
Not Applicable
Width:
1.77";Trip Class - Overload=10"
Number of Poles:
3
Reset Type - Relay:
Auto, Manual
Sensing Method:
Bimetallic
Height:
2.56";Depth=2.28""
For Use With:
TeSys K AC or DC IEC Contactor
Body Depth - Relay:
2.56 in
Overall Height - Relay:
2.28 in
Standards:
BS 4941, IEC 60947, NF C 63-650, REACH, RoHS, VDE 0660
Body Width - Relay:
1.77 in
Body Height - Relay:
2.28 in
Features:
Single Phase Sensitivity; Differential
Trip Class:
10A
Starter Type:
IEC
Operating Altitude:
6561.68 ft (2000 m) without derating
Power Dissipation Per Pole:
2 W
Phase Failure Sensitivity:
yes IEC 60947-4-1
[Ith] Conventional Free Air Thermal Current:
6 A signalling circuit
Connections - Terminals:
screw clamp terminals 1 1.5-4 mm²solid || screw clamp terminals 2 1.5-4 mm²solid || screw clamp terminals 1 0.75-4 mm²flexible without cable end || screw clamp terminals 2 0.75-4 mm²flexible without cable end || screw clamp terminals 1 0.34-2.5 m
Product Name:
TeSys LRK
Product Compatibility:
LP4K || LC1K || LC7K || LP1K
Mechanical Robustness:
shocks NO contact10 Gn for 11 ms IEC 60068-2-27 || shocks NC contact10 Gn for 11 ms IEC 60068-2-27 || vibrations NO contact2 Gn, 5 to 300 Hz IEC 60068-2-6 || vibrations NC contact2 Gn, 5 to 300 Hz IEC 60068-2-6
Associated Fuse Rating:
6 A gG signalling circuit VDE 0660 || 6 A gG signalling circuit IEC 60947
[Uimp] Rated Impulse Withstand Voltage:
6 kV
[Ui] Rated Insulation Voltage:
power circuit 690 V BS 4941 || power circuit 690 V IEC 60947 || power circuit 750 V VDE 0110 group C || power circuit 600 V CSA C22.2 No 14
[Ue] Rated Operational Voltage:
<= 690 V power circuit || 690 V AC AC-15 signalling circuit || 250 V DC DC-13 signalling circuit
Network Frequency:
<= 400 Hz
Mounting Support:
under contactor || plate, with specific accessories || rail, with specific accessories
Control Type:
Red push-button trip test function || Blue push-button stop and manual reset || selector switch manual or automatic reset
Local Signalling:
trip indicator Yellow)
Thermal Protection Adjustment Range:
1.8-2.6 A
Flame Retardance:
V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
Fire Resistance:
850°C IEC 60695-2-1
Relay Application:
motor protection
Range:
TeSys
Protective Treatment:
TC IEC 60068 || TC DIN 50016
Thermal Overload Class:
class 10A IEC 60947-4-1
Product Or Component Type:
differential thermal overload relay
Device Short Name:
LR2K
Auxiliary Contact Composition:
1 NO + 1 NC
Network Type:
DC || AC
Ambient Air Temperature For Storage:
-40-70°C
Product Certifications:
UL || CSA || UKCA
Ambient Air Temperature For Operation:
-20-55°C without derating IEC 60947 || -30-60°C with derating IEC 60947
Tightening Torque:
1.3 N.m screw clamp terminals Philips No 2 || 1.3 N.m screw clamp terminals flat Ø 6 mm || 1.3 N.m screw clamp terminals pozidriv No 2
Ip Degree Of Protection:
IP2X conforming to IEC 60529
Includes Mounting Hardware:
Not Applicable
Body Width:
1.77 in
Body Depth:
2.56 in
Compatible with Series:
TeSys Deca, TeSys K
Relay Style:
IEC
Auxiliary Contact Form:
1NO/1NC
IP Rating:
IP22
Maximum Overload Relay Current Setting:
2.6 A
Maximum Operating Temperature:
131 Degrees F
Mounting Style:
Direct To Contactor
Overall Height:
2.28 in
Overload Protection Type:
Thermal
Minimum Operating Temperature:
-4 Degrees F
Reset Type:
Auto, Manual
Body Height:
2.28 in
Maximum Voltage Rating:
250V DC (Signaling Circuit), 690V AC (Signaling Circuit)
Terminal Connection Type:
Screw Clamp Terminals
Minimum Overload Relay Current Setting:
1.8 A
Package Quantity:
1