- Country of Origin:
- Mexico
- Item:
- Molded Case Circuit Breaker
- Series:
- HJL
- Amps:
- 100A
- Number of Poles:
- 3
- AC Voltage Rating:
- 600V AC
- Circuit Breaker Type:
- Standard
- Circuit Breaker Actuator:
- Toggle
- Circuit Breaker Mounting Style:
- Unit Mount
- Max. AIR Rating:
- 100kA at 240V AC
- Trip Type:
- Thermal Magnetic
- Instantaneous Trip:
- Fixed
- Terminal Connection:
- Line/Load Lug
- Frame Size:
- 150A/HJ
- Width:
- 4.12 in
- Depth:
- 4.36 in
- Height:
- 6.4 in
- DC Voltage Rating:
- 250V DC
- Max. Wire Size:
- 3/0 AWG (Cu/Al)
- Min. Wire Size:
- 14 AWG (Cu/Al)
- Interrupt Rating:
- 65 kA at 220/240/480V AC, 35 kA at 380/440/415V AC, 18 kA at 500/525V AC, 20 kA at 250/500V DC, 100 kA at 240V AC, 25 kA at 600V AC
- High Amp Trip Setting:
- 1700 A
- Standards:
- UL, CSA, NEMA, NOM, CE
- Application:
- HACR rated Applications; Distribution
- Color:
- Black
- Features:
- Mercury Free; PVC Free
- Operating Altitude:
- Less than 6561.68 ft (2000 m) without derating; 5000 m with derating
- Number Of Slots:
- 2 auxiliary switch OF plug-in); 1 alarm switch SD plug-in); 1 overcurrent trip switch SDE plug-in); 1 voltage release MN or MX plug-in)
- Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- Power Wire Stripping Length:
- 0.63 in (16 mm)
- Communication Interface:
- Modbus; Ethernet
- Tightening Torque:
- 44.25 lbf.in (5 N.m) 0.00 to 0.01 in² (2.5 to 6 mm²) (AWG 14 to AWG 10); 123.91 lbf.in (14 N.m) 0.02 to 0.15 in² (10 to 95 mm²) (AWG 8 to AWG 3/0)
- Pollution Degree:
- 3 IEC 60947-1
- Rated Insulation Voltage:
- 750 V IEC 60947-2
- Terminal Identifier:
- AL150HD
- Local Signalling:
- Switched off (OFF) 1 trip indicator green)
- Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Network Frequency:
- 50/60 Hz
- Quality Labels:
- CE
- Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2; 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2; 18 kA 500/525 V AC 50/60 Hz IEC 60947-2; 20 kA 250 V DC IEC 60947-2; 20 kA 500 V DC IEC 60947-2
- IP Degree Of Protection:
- Front cover IP40 IEC 60529
- Circuit Breaker Application:
- HACR rated
- Ambient Air Temperature For Operation:
- 28 to 158°F (-2 to 70°C)
- Continuous Current Rating:
- 0.8
- Ambient Air Temperature For Storage:
- -58 to 185°F (-50 to 85°C)
- Breaking Capacity:
- 100 kA 240 V AC 50/60 Hz UL 489; 65 kA 480 V AC 50/60 Hz UL 489; 25 kA 600 V AC 50/60 Hz UL 489; 20 kA 250 V DC UL 489
- Suitability For Isolation:
- Yes IEC 60947-2
- Utilisation Category:
- Category A
- Protected Poles Description:
- 3t
- Magnetic Hold Current:
- 900 A
- Device Application:
- Distribution
- Product Name:
- PowerPact H
- AWG Gauge:
- AWG 14 to AWG 3/0 aluminium/copper terminal
- Breaking Capacity Code:
- J
- Product Certifications:
- UL; CSA; NOM
- Package Quantity:
- 1