- Country of Origin:
- France
- Operator:
- Selector Switch
- NEMA Size:
- Not Applicable
- Enclosure NEMA Rating:
- No Enclosure
- Depth:
- 4.4 in
- Height:
- 4.7 in
- Overload Relay Amp Setting:
- 30 to 40A
- Amps AC:
- 30 to 40
- Width:
- 2.4 in
- Item:
- Manual Motor Starter
- Number of Poles:
- 3
- Max. Voltage:
- 600V AC
- HP @ 3 Phase - 480V:
- 25 hp
- HP @ 3 Phase - 240V:
- 10 hp
- HP @ 1 Phase - 120V:
- 3 hp
- Pilot Light:
- No
- Standards:
- ATEX Compliant, BV, CCC, CSA, DNV-GL, EAC, EN/IEC 60947-2, EN/IEC 60947-4, LROS, RINA, UKCA, UL Listed
- Description/Special Features:
- Class 10 Ambient-Compensated Thermal Overload Relay
- HP @ 1 Phase - 230V:
- 5 hp
- HP @ 3 Phase - 575V:
- 30 hp
- Phase Loss Sensitivity:
- Yes
- HP @ 3 Phase - 460-575V:
- 30
- HP @ 3 Phase - 208V:
- 10 hp
- Trip Unit Technology:
- thermal-magnetic
- Product Certifications:
- CCC || UL || CSA || EAC || ATEX || LROS (Lloyds register of shipping) || BV || ABS || DNV-GL || UKCA
- Fire Resistance:
- 960°C IEC 60695-2-11
- Poles Description:
- 3P
- [Ith] Conventional Free Air Thermal Current:
- 40 A IEC 60947-4-1
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947-2
- Ik Degree Of Protection:
- IK09 enclosure
- Line Rated Current:
- 40 A
- Product Name:
- TeSys GV3 || TeSys Deca
- Control Type:
- rotary handle
- [Ui] Rated Insulation Voltage:
- 690 V AC 50/60 Hz IEC 60947-2
- Network Frequency:
- 50/60 Hz IEC 60947-4-1
- Color:
- dark grey
- Product Or Component Type:
- motor circuit breaker
- Device Application:
- motor protection
- Range:
- TeSys Deca
- Power Dissipation Per Pole:
- 8 W
- Tightening Torque:
- 5 N.m screw clamp terminal
- Motor Power Kw:
- 18.5-18.5 kW 400/415 V AC 50/60 Hz || 22-22 kW 500 V AC 50/60 Hz || 37-37 kW 690 V AC 50/60 Hz
- Magnetic Tripping Current:
- 560-560 A
- Ambient Air Temperature For Operation:
- -20-60°C
- Operating Altitude:
- 9842.52 ft (3000 m)
- Electrical Durability:
- 50000 cycles AC-3 415 V In
- Mechanical Robustness:
- shocks 15 Gn for 11 ms contactor open || shocks 30 Gn for 11 ms contactor closed || vibrations 4 Gn, 5...300 Hz
- Thermal Protection Adjustment Range:
- 30-40 A IEC 60947-4-1
- Phase Failure Sensitivity:
- yes IEC 60947-4-1
- Device Short Name:
- GV3P
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-2
- Suitability For Isolation:
- yes IEC 60947-1
- Utilisation Category:
- AC-3 IEC 60947-4-1
- Ip Degree Of Protection:
- IP20 IEC 60529
- Network Type:
- AC
- Breaking Capacity:
- 100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 || 50 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 || 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 12 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 6 kA Icu 690 V AC 50/60 Hz IEC 60947-2
- [Ics] Rated Service Short-Circuit Breaking Capacity:
- 100 % 230/240 V AC 50/60 Hz IEC 60947-2 || 100 % 400/415 V AC 50/60 Hz IEC 60947-2 || 100 % 440 V AC 50/60 Hz IEC 60947-2 || 50 % 500 V AC 50/60 Hz IEC 60947-2 || 50 % 690 V AC 50/60 Hz IEC 60947-2
- Mechanical Durability:
- 50000 cycles
- Rated Duty:
- continuous IEC 60947-4-1
- Ambient Air Temperature For Storage:
- -40-80°C
- Climatic Withstand:
- IACS E10
- Fixing Mode:
- 35 mm symmetrical DIN rail clipped || panel screwed with 3 x M4 screws)
- Mechanical Operating Durability:
- 50,000
- Terminal Connection Type:
- Screw Clamp Terminals
- Horsepower @ Single Phase - 120V AC:
- 3 hp
- IP Rating:
- IP20
- Phase:
- Three
- Frequency:
- 50/60 Hz
- Electrical Operating Durability:
- 50,000
- Mounting Style:
- DIN Rail
- Overall Height:
- 5.2 in
- Overload Protection Type:
- Thermal
- Maximum Operating Temperature:
- 140 Degrees F
- Horsepower @ Three Phase - 480V AC:
- 25 hp
- Overall Width:
- 2.17 in
- Starter Style:
- IEC
- Resistance Properties:
- Fire Resistant
- Horsepower @ Three Phase - 208V AC:
- 10 hp
- Current AC:
- 40 A
- Horsepower @ Three Phase - 240V AC:
- 10 hp
- Overall Depth:
- 5.35 in
- Horsepower @ Single Phase - 240V AC:
- 5 hp
- Maximum Voltage Rating:
- 600V AC
- Minimum Operating Temperature:
- -4 Degrees F
- Includes Pilot Light:
- No
- Minimum Overload Relay Current Setting:
- 30 A
- Series:
- TeSys Deca
- Maximum Overload Relay Current Setting:
- 40 A
- Horsepower @ Three Phase - 600V AC:
- 30 hp
- NEMA Enclosure Rating:
- No Enclosure
- Rated Service Short-Circuit Breaking Capacity:
- 100% 230/240 V AC 50/60 Hz IEC 60947-2; 100% 400/415 V AC 50/60 Hz IEC 60947-2; 100% 440 V AC 50/60 Hz IEC 60947-2; 50% 500 V AC 50/60 Hz IEC 60947-2; 50% 690 V AC 50/60 Hz IEC 60947-2
- Package Quantity:
- 1