IEC Magnetic Contactor, 3 Poles, 24 V AC, 115 A, Reversing: No - LC1D115B7

Square D
SKU:
LC1D115B7
|
UPC:
785901549604
Availability:
In Stock

Log in for pricing

(No reviews yet)
Current Stock:
IEC Magnetic Contactor, Auxiliary Contact Form 1NO/1NC, NEMA Enclosure Rating No Enclosure, NEMA Size Not Applicable, Coil Voltage 24V AC, Number of Poles 3, Full Load Current - Inductive 115 A, Full Load Current - Resistive 200 A, Reversing Capability Non-Reversing, Overall Height 6.22 in, Overall Width 0.47 in, Terminal Connection Type Screw Clamp Terminals, Mounting Style DIN Rail, Plate, Series TeSys Deca, Number of Auxillary Contacts 2, Contactor Style IEC
Country of Origin:
Czechia
Item:
IEC Magnetic Contactor
Full Load Amps-Inductive:
115 A
Action:
Non-Reversing
Full Load Amps-Resistive:
200 A
Number of Poles:
3
Coil Volts:
24 V AC
Reversing:
No
Height:
4.33 in
HP @ 3 Phase - 208V:
30 hp
Width:
4.72 in
HP @ 3 Phase - 240V:
40 hp
Depth:
6.22 in
HP @ 3 Phase - 575V:
100 hp
HP @ 3 Phase - 480V:
75 hp
Enclosure NEMA Rating:
No Enclosure
Aux. Contact Configuration:
1NO/1NC
Hz:
50/60
Auxiliary Contact Form:
1NO/1NC
Standards:
BV, CCC, CSA, CSA C22.2 No 14, DNV, EN 60947-4-1, EN 60947-5-1, GL, GOST, IEC 60947-4-1, IEC 60947-5-1, LROS, RINA, UKCA, UL 508, UL Listed
Series:
TeSys Deca
NEMA Size:
Not Applicable
Shock Resistance:
15 G for 11 ms (Contactor Closed), 6 G for 11 ms (Contactor Open)
Net Weight:
2.5 kg
Operating Speed:
2400 cycles per hr
Electrical Connection:
Screw Clamp Terminals
Electrical Durability:
0.8 Mcycles (200 A, AC-1, Less than 440 V); 0.95 Mcycles (115 A, AC-3, Less than 440 V); 0.95 Mcycles (115 A, AC-3e, Less than 440 V)
Control Circuit Voltage Limits:
Drop-Out AC
Application:
Motor Control, Resistive Load
Features:
Built-In Bi-Directional Peak Limiting Diode Suppressor
Insulation Resistance Range:
Greater Than 10 MOhms (Signalling Circuit)
Rated Making Capacity:
1260 A @ 440V (Power Circuit), 140 A (AC Signalling Circuit), 250 A (DC Signalling Circuit)
Rated Insulation Volts:
600/1000V (Power Circuit), 600/690V (Signalling Circuit)
Fire Rating:
UL 94 V1
Includes Protective Cover:
Yes
Rated Breaking Capacity:
1100 A @ 440V
Impedance:
0.6 mOhm
Working Height:
Up to 9842.52 ft
Switching Current:
5 mA (Signalling Circuit)
Impulse Withstand Voltage:
8 kV
Rated Voltage:
1000V AC, 300V DC
Mounts On:
Plate, Rail
Watts Loss:
3 to 8W
Signalling Circuit Frequency:
25 to 400 Hz
Mechanical Durability:
8 Mcycles
Tightening Torque:
1.2 Nm (Control Circuit), 12 Nm (Power Circuit)
Fuse Amps:
250 A (Type 1 Power Circuit), 200 A (Type 2 Power Circuit), 10 A (Signalling Circuit)
Hold VA:
2 to 18 VA
Switching Voltage:
17 V (Signalling Circuit)
Max. Operating Watts:
30 kW (at 220 to 230V AC 50/60 Hz AC-3), 55 kW (at 380 to 400V AC 50/60 Hz AC-3), 59 kW 415 to (at 440V AC 50/60 Hz AC-3), 75 kW (at 500V AC 50/60 Hz AC-3), 80 kW (at 660 to 690V AC 50/60 Hz AC-3), 65 kW (at 1000V AC 50/60 Hz AC-3), 18.5 kW (at 400V
Non-Overlap Time:
1.5 ms
Vibration Resistance:
4 G (Contactor Closed), 2 G (Contactor Open)
Environmental Attributes:
Mercury Free, PVC Free, Pollution Degree 3
Operating Time:
6 to 20 ms (Opening), 20 to 50 ms (Closing)
Max. Temperature:
850°C
Rated Short-Time Withstand Current:
250 A (at 40°C for 10 min Power Circuit), 550 A (at 40°C for 1 min Power Circuit), 950 A (at 40°C for 10 s Power Circuit), 1100 A (at 40°C for 1 s Power Circuit), 100 A (For 1 s Signalling Circuit), 120 A (For 500 ms Signalling Circuit), 140 A (F
Inrush VA:
280 to 350 VA
Overvoltage Category:
CAT III
IP Rating:
IP20
Thermal Amperage:
200 A (at 60°C Power Circuit)
Resistance Properties:
Fire Resistant, Insulation Resistant
Embedded Surge Suppressor:
Yes
Horsepower @ Three Phase - 208V AC:
30 hp
Horsepower @ Three Phase - 480V AC:
75 hp
Overall Width:
0.47 in
Phase:
Three
NEMA Enclosure Rating:
No Enclosure
Reversing Capability:
Non-Reversing
Contactor Style:
IEC
Horsepower @ Three Phase - 240V AC:
40 hp
Minimum Operating Temperature:
-40 Degrees F
Number of Normally Open Main Contacts:
3
Coil Voltage:
24V AC
Includes Auxiliary Contacts:
Yes
Mechanical Operating Durability:
8,000,000
Frequency:
50/60 Hz
Full Load Current - Inductive:
115 A
Electrical Operating Durability:
800,000, 950,000
Overall Height:
6.22 in
Horsepower @ Three Phase - 600V AC:
100 hp
Number of Auxillary Contacts:
2
NEMA Enclosure Material:
Not Applicable
Maximum Voltage Rating:
1000V AC
Mounting Style:
DIN Rail, Plate
Terminal Connection Type:
Screw Clamp Terminals
Maximum Operating Temperature:
140 Degrees F
Full Load Current - Resistive:
200 A
Overall Depth:
5.35 in
Horsepower @ Single Phase - 240V AC:
1 hp
Protective Cover:
With
Climatic Withstand:
IACS E10 exposure to damp heat; IEC 60947-1 Annex Q category D exposure to damp heat
Poles Description:
3P
Coil Technology:
Built-in bidirectional peak limiting diode suppressor
Protective Treatment:
THIEC 60068-2-30
Associated Fuse Rating:
250 A gG at Less than or Equal to 690 V coordination type 1 for power circuit; 200 A gG at Less than or Equal to 690 V coordination type 2 for power circuit; 10 A gG for signalling circuit
Rated Operational Current:
200 A (at Less than 140°F (60°C)) at Less than or Equal to 440 V AC AC-1 for power circuit; 115 A (at Less than 140°F (60°C)) at Less than or Equal to 440 V AC AC-3 for power circuit; 115 A (at Less than 140°F (60°C)) at Less than or Equal to 4
Product Certifications:
DNV; GOST; UL; CSA; CCC; LROS (Lloyds register of shipping); RINA; GL; BV; UKCA; CE
Fire Resistance:
1562°F (850°C) IEC 60695-2-1
Permissible Ambient Air Temperature Around The Device:
-40 to 140°F (-40 to 60°C); 140 to 158°F (60 to 70°C) with derating
Auxiliary Contacts Type:
Mechanically linked 1 NO + 1 NC IEC 60947-5-1; Mirror contact 1 NC IEC 60947-4-1
Average Impedance:
0.6 mOhm - Ith 200 A 50 Hz for power circuit
Mounting Support:
Rail; Plate
Motor Power KW:
30 kW at 220 to 230 V AC 50/60 Hz (AC-3); 55 kW at 380 to 400 V AC 50/60 Hz (AC-3); 59 kW at 415 to 440 V AC 50/60 Hz (AC-3); 75 kW at 500 V AC 50/60 Hz (AC-3); 80 kW at 660 to 690 V AC 50/60 Hz (AC-3); 65 kW at 1000 V AC 50/60 Hz (AC-3); 18.5 kW at
Control Circuit Voltage:
24 V AC 50/60 Hz
Compatibility Code:
LC1D
Control Circuit Type:
AC 50/60 Hz standard
Rated Insulation Voltage:
Power circuit 600 V CSA; Power circuit 600 V UL; Power circuit 1000 V IEC 60947-4-1; Signalling circuit 690 V IEC 60947-1; Signalling circuit 600 V CSA; Signalling circuit 600 V UL
Maximum Horse Power Rating:
30 hp at 200/208 V AC 50/60 Hz for 3 phase motors; 40 hp at 230/240 V AC 50/60 Hz for 3 phase motors; 75 hp at 460/480 V AC 50/60 Hz for 3 phase motors; 100 hp at 575/600 V AC 50/60 Hz for 3 phase motors
Conventional Free Air Thermal Current:
200 A (at 140°F (60°C)) for power circuit
Utilisation Category:
AC-1; AC-4; AC-3; AC-3e
Product Or Component Type:
Contactor
Rated Operational Voltage:
Power circuit Less than or Equal to 1000 V AC 25 to 400 Hz; Power circuit Less than or Equal to 300 V DC
Inrush Power in VA:
280 to 350 VA 60 Hz cos phi 0.8 (at 68°F (20°C)); 280 to 350 VA 50 Hz cos phi 0.8 (at 68°F (20°C))
Insulation Resistance:
Greater than 10 MOhm for signalling circuit
Auxiliary Contact Composition:
1 NO + 1 NC
Minimum Switching Voltage:
17 V for signalling circuit
Maximum Operating Rate:
2400 cyc/h 140°F (60°C)
Minimum Switching Current:
5 mA for signalling circuit
Safety Reliability Level:
B10d = 684932 cycles contactor with nominal load EN/ISO 13849-1; B10d = 10000000 cycles contactor with mechanical load EN/ISO 13849-1
Rated Impulse Withstand Voltage:
8 kV IEC 60947
Pollution Degree:
3
Heat Dissipation:
3 to 8 W at 50/60 Hz
Operating Altitude:
0 to 9842.52 ft (0 to 3000 m)
Hold-In Power Consumption in VA:
2 to 18 VA 60 Hz cos phi 0.3 (at 68°F (20°C)); 2 to 18 VA 50 Hz cos phi 0.3 (at 68°F (20°C))
Contact Compatibility:
M13
Mechanical Robustness:
Vibrations contactor open 2 Gn, 5 to 300 Hz); Vibrations contactor closed 4 Gn, 5 to 300 Hz); Shocks contactor closed 15 Gn for 11 ms); Shocks contactor open 6 Gn for 11 ms)
IRMS Rated Making Capacity:
1260 A at 440 V for power circuit conforming to IEC 60947; 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1
Rated Short Time Withstand Current:
250 A 104°F (40°C) - 10 min for power circuit; 550 A 104°F (40°C) - 1 min for power circuit; 950 A 104°F (40°C) - 10 s for power circuit; 1100 A 104°F (40°C) - 1 s for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for sign
Connections - Terminals:
Control circuit
Flame Retardance:
V1 conforming to UL 94
Pole Contact Composition:
3 NO
Power Dissipation Per Pole:
24 W AC-1; 7.9 W AC-3; 7.9 W AC-3e
IP Degree Of Protection:
IP20 front face IEC 60529
Contactor Application:
Motor control; Resistive load
Package Quantity:
1