- Country of Origin:
- Czechia
- Item:
- IEC Magnetic Contactor
- Full Load Amps-Inductive:
- 150 A
- Full Load Amps-Resistive:
- 200 A
- Number of Poles:
- 3
- Coil Volts:
- 110 V AC
- Height:
- 158 mm
- HP @ 3 Phase - 208V:
- 40 hp
- Width:
- 120 mm
- HP @ 3 Phase - 575V:
- 125 hp
- HP @ 3 Phase - 240V:
- 50 hp
- Depth:
- 136 mm
- HP @ 3 Phase - 480V:
- 100 hp
- Aux. Contact Configuration:
- 1NO/1NC
- Standards:
- CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508, CCC, GOST, DNV, UL, LROS, BV, GL, RINA, CSA, UKCA, CE, THIEC 60068-2-30
- Series:
- LC1D
- Rated Breaking Capacity:
- 1400 A @ 440V
- Environmental Attributes:
- Mercury Free, PVC Free, Pollution Degree 3
- Vibration Resistance:
- 4 G (Contactor Closed), 2 G (Contactor Open)
- Operating Time:
- 20 to 35 ms (Closing), 40 to 75 ms (Opening)
- Features:
- Built-In Bi-Directional Peak Limiting Diode Suppressor
- Max. Operating Watts:
- 40 kW (at 220 to 230V AC 50/60 Hz AC-3), 75 kW (at 380 to 400V AC 50/60 Hz AC-3), 80 kW 415 to (at 440V AC 50/60 Hz AC-3), 90 kW (at 500V AC 50/60 Hz AC-3), 100 kW (at 660 to 690V AC 50/60 Hz AC-3), 75 kW (at 1000V AC 50/60 Hz AC-3), 22 kW (at 400V A
- Electrical Connection:
- Screw Clamp Terminals
- Includes Protective Cover:
- Yes
- Hold VA:
- 2 to 18 VA
- Fuse Amps:
- 10 A (Signalling Circuit), 315 A (Type 1 Power Circuit), 250 A (Type 2 Power Circuit)
- Overvoltage Category:
- CAT III
- Fire Rating:
- UL 94 V1
- Operating Speed:
- 1200 cycles per hr
- Watts Loss:
- 3 to 4.5W
- Max. Temperature:
- 850°C
- Working Height:
- Up to 9842.52 ft
- Insulation Resistance Range:
- Greater Than 10 MOhms (Signalling Circuit)
- Application:
- Motor Control, Resistive Load
- Inrush VA:
- 280 to 350 VA
- IP Rating:
- IP20
- Electrical Durability:
- 0.85 Mcycles (150 A, AC-3, Less than 440 V); 1 Mcycles (200 A, AC-1, Less than 440 V); 0.85 Mcycles (150 A, AC-3e, Less than 440 V)
- Signalling Circuit Frequency:
- 25 to 400 Hz
- Switching Voltage:
- 17 V (Signalling Circuit)
- Mechanical Durability:
- 8 Mcycles
- Tightening Torque:
- 1.2 Nm (Control Circuit), 12 Nm (Power Circuit)
- Impedance:
- 0.6 mOhm
- Rated Insulation Volts:
- 600/1000V (Power Circuit), 600/690V (Signalling Circuit)
- Rated Voltage:
- 1000V AC, 300V DC
- Impulse Withstand Voltage:
- 8 kV
- Rated Making Capacity:
- 140 A (AC Signalling Circuit), 250 A (DC Signalling Circuit), 1660 A @ 440V (Power Circuit)
- Non-Overlap Time:
- 1.5 ms
- Thermal Amperage:
- 200 A (at 60°C Power Circuit)
- Switching Current:
- 5 mA (Signalling Circuit)
- Net Weight:
- 2.5 kg
- Mounts On:
- Plate, Rail
- Shock Resistance:
- 15 G for 11 ms (Contactor Closed), 6 G for 11 ms (Contactor Open)
- Control Circuit Voltage Limits:
- Drop-Out AC
- Rated Short-Time Withstand Current:
- 250 A (at 40°C for 10 min Power Circuit), 580 A (at 40°C for 1 min Power Circuit), 1200 A (at 40°C for 10 s Power Circuit), 1400 A (at 40°C for 1 s Power Circuit), 100 A (For 1 s Signalling Circuit), 120 A (For 500 ms Signalling Circuit), 140 A (
- Control Circuit Type:
- AC 50/60 Hz standard
- Rated Insulation Voltage:
- Power circuit 600 V CSA; Power circuit 600 V UL; Power circuit 1000 V IEC 60947-4-1; Signalling circuit 690 V IEC 60947-1; Signalling circuit 600 V CSA; Signalling circuit 600 V UL
- Control Circuit Voltage:
- 110 V AC 50/60 Hz
- Maximum Horse Power Rating:
- 40 hp at 200/208 V AC 50/60 Hz for 3 phase motors; 50 hp at 230/240 V AC 50/60 Hz for 3 phase motors; 100 hp at 460/480 V AC 50/60 Hz for 3 phase motors; 125 hp at 575/600 V AC 50/60 Hz for 3 phase motors
- Hold-In Power Consumption in VA:
- 2 to 18 VA 60 Hz cos phi 0.9 (at 68°F (20°C)); 2 to 18 VA 50 Hz cos phi 0.9 (at 68°F (20°C))
- Permissible Ambient Air Temperature Around The Device:
- -40 to 140°F (-40 to 60°C); 140 to 158°F (60 to 70°C) with derating
- Rated Operational Voltage:
- Power circuit Less than or Equal to 1000 V AC 25 to 400 Hz; Power circuit Less than or Equal to 300 V DC
- Product Or Component Type:
- Contactor
- Mounting Support:
- Plate; Rail
- Protective Cover:
- With
- Maximum Operating Rate:
- 1200 cyc/h 140°F (60°C)
- Associated Fuse Rating:
- 10 A gG for signalling circuit conforming to IEC 60947-5-1; 315 A gG at Less than or Equal to 690 V coordination type 1 for power circuit; 250 A gG at Less than or Equal to 690 V coordination type 2 for power circuit
- Climatic Withstand:
- IACS E10 exposure to damp heat
- Contact Compatibility:
- M13
- Operating Altitude:
- 0 to 9842.52 ft (0 to 3000 m)
- Minimum Switching Voltage:
- 17 V for signalling circuit
- Flame Retardance:
- V1 conforming to UL 94
- Rated Impulse Withstand Voltage:
- 8 kV IEC 60947
- Pole Contact Composition:
- 3 NO
- Auxiliary Contacts Type:
- Mechanically linked 1 NO + 1 NC IEC 60947-5-1; Mirror contact 1 NC IEC 60947-4-1
- Heat Dissipation:
- 3 to 4.5 W at 50/60 Hz
- Mechanical Robustness:
- Vibrations contactor open 2 Gn, 5 to 300 Hz); Vibrations contactor closed 4 Gn, 5 to 300 Hz); Shocks contactor closed 15 Gn for 11 ms); Shocks contactor open 6 Gn for 11 ms)
- Average Impedance:
- 0.6 mOhm - Ith 200 A 50 Hz for power circuit
- Product Certifications:
- CCC; GOST; DNV; UL; LROS (Lloyds register of shipping); BV; GL; RINA; CSA; UKCA; CE
- IRMS Rated Making Capacity:
- 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1; 1660 A at 440 V for power circuit conforming to IEC 60947
- Pollution Degree:
- 3
- Insulation Resistance:
- Greater than 10 MOhm for signalling circuit
- Coil Technology:
- Built-in bidirectional peak limiting diode suppressor
- Rated Operational Current:
- 200 A (at Less than 140°F (60°C)) at Less than or Equal to 440 V AC AC-1 for power circuit; 150 A (at Less than 140°F (60°C)) at Less than or Equal to 440 V AC AC-3 for power circuit; 150 A (at Less than 140°F (60°C)) at Less than or Equal to 4
- IP Degree Of Protection:
- IP20 front face IEC 60529
- Poles Description:
- 3P
- Utilisation Category:
- AC-4; AC-3; AC-1; AC-3e
- Fire Resistance:
- 1562°F (850°C) IEC 60695-2-1
- Rated Short Time Withstand Current:
- 250 A 104°F (40°C) - 10 min for power circuit; 580 A 104°F (40°C) - 1 min for power circuit; 1200 A 104°F (40°C) - 10 s for power circuit; 1400 A 104°F (40°C) - 1 s for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for sig
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Motor Power KW:
- 40 kW at 220 to 230 V AC 50/60 Hz (AC-3); 75 kW at 380 to 400 V AC 50/60 Hz (AC-3); 80 kW at 415 to 440 V AC 50/60 Hz (AC-3); 90 kW at 500 V AC 50/60 Hz (AC-3); 100 kW at 660 to 690 V AC 50/60 Hz (AC-3); 75 kW at 1000 V AC 50/60 Hz (AC-3); 22 kW at 4
- Conventional Free Air Thermal Current:
- 200 A (at 140°F (60°C)) for power circuit
- Inrush Power in VA:
- 280 to 350 VA 60 Hz cos phi 0.9 (at 68°F (20°C)); 280 to 350 VA 50 Hz cos phi 0.9 (at 68°F (20°C))
- Contactor Application:
- Motor control; Resistive load
- Safety Reliability Level:
- B10d = 684932 cycles contactor with nominal load EN/ISO 13849-1; B10d = 10000000 cycles contactor with mechanical load EN/ISO 13849-1
- Minimum Switching Current:
- 5 mA for signalling circuit
- Connections - Terminals:
- Control circuit
- Protective Treatment:
- THIEC 60068-2-30
- Power Dissipation Per Pole:
- 24 W AC-1; 13.5 W AC-3; 13.5 W AC-3e
- Package Quantity:
- 1